How to Buy?

Why PITE 3830?
Cost can be tremendous upon bad insulation or grounding in the power system. It may even cause power break-off which is costly to repair. Fast localization and elimination of insulation faults will be significant for electricians and technicians. It is also required by DIN VDE 0100-410 (VDE 0100-410):
2007-06 chapter 411.6.3.1 and IEC 60364-4-41 chapter 413.1.5.4. PITE 3830 is developed to fast detect, track and locate virtual grounding faults on DC systems. This spares you from hours of unnecessary troubleshooting and helps to increase the reliability of your electrical equipment. It is widely used in locomotive, telecom, power utilities, etc.
Methods
There is loose of electricity to the ground in the breakage of busbar and thus generate a faulty "grounding". When testing leads of PITE 3830 are connected to the ground and busbar, there will be a return circuit. Signal generator (main unit) will send a low-frequency voltage signal of 0.1Hz~1000Hz between the testing target and grounding malfunctioned circuit. The breaking point will generate leaking current. As the grounding receiver (signal receiver) moves in the circuit, different points in the circuit will have different reaction in the indication of sound warning. It will pinpoint the cable fault basing on the sound volume in the signal receiver.

This is the flowchart for ground-fault location in DC system.
It indicates the cable connection and simple way to pinpoint faulty "Grounding".
Features
Two function in one: Insulation tester and ground fault locator
.Parameter
|
Measuring range
|
V testing: 0.00-1000V
Insulation resistance: 20kΩ-500MΩ (250V) 50kΩ-1000MΩ (500V) 100 kΩ-2000MΩ (1000V) |
||
|
Min resolution
|
Voltage: 0.1V Insulation R: 0.01 MΩ
|
||
|
Accuracy
|
Voltage: 1%rdg±8dgt
Insulation R: 0.5 MΩ-100 MΩ 5%rdg±6dgt ﹥100 MΩ: 10%rdg±6dgt |
||
|
Output signal
|
voltage: 0-1000V±10% Frequency: 1-1000Hz
|
||
|
Power consumption
|
≥4 hours(continuous operation)
|
||
|
Memory
|
32k×8bit Non Volatile SRAM
|
||
|
Displaying screen
|
128×64 pixels LCD
|
||
|
Communication
|
USB interface
|
Battery
|
Li-ion
|
|
Dimension
|
490*370*250mm
|
Weight
|
7KG
|
|
Humidity
|
80%R.H
|
Temperature
|
-5℃-40℃
|
|
Receiver
|
|
||
|
Testing accuracy
|
≤0.25MΩ
|
Power voltage
|
DC 8.4V
|
|
Sensor aperture
|
59mm
|
Jaw opening
|
66mm
|
Related Products